project
|
Standard
|
Power Supply
|
Rated input voltage
|
Single-phase 220V, three-phase 220V, 380V, 660V + 20%, 50-60Hz + 5%.
|
output
|
Rated output voltage
|
Three-phase 220V, 380V, 660V (maximum output voltage is the same as input power supply voltage)
|
Quota
|
100% continuous
|
Maximum overload current
|
150% 1 minute, 180% 0.2 seconds
|
control
system
and
transport
That's ok
|
Output Voltage Automatic Adjustment
|
When the AVR function is effective, the output voltage is basically unchanged and the constant V/f value is maintained when the input voltage varies.
|
control mode
|
Optimized Space Voltage Vector Control PWM
|
Frequency control range
|
0~400Hz
|
Output frequency accuracy
|
Maximum frequency value (+0.1%)
|
Output Frequency Resolution
|
0.01Hz
|
Voltage / frequency characteristics
|
The rated voltage can be adjusted from 50% to 100%, and the fundamental frequency can be adjusted at 50Hz.
|
Torque rise
|
The 21 way is optional.
|
Acceleration and deceleration characteristics
|
0.1-3600 seconds (up to 36,000 seconds)
|
Braking torque
|
Within 22KW > 20%, over 30KW > 15%.
|
Frequency setting input
|
Keyboard, keyboard potentiometer, 0 ~ 5V, 0 ~ 10V, 4 ~ 20mA and 11 combinations among them, PC serial communication settings, built-in PI regulator
|
Input command signal
|
FWD, REV and 6-way programmable input terminals, 19 functions are optional, such as forward/reverse point motion, multi-segment speed, multi-segment acceleration/deceleration time, free parking, voltage/current switching, etc.
|
PG signal input
|
A+, A-, B+, B-differential input/A-, B-open collector input
|
Serial communication interface
|
RS485/RS232 interface
|
Standard function
|
Current Limit, Torque Lift, Speed Tracking, DC Braking, Power Outage Restart, Slip Compensation, Fault Auto-Reset, Frequency Limit, Bias Frequency, Start Frequency, Jump Frequency, Frequency Gain, Carrier Frequency Adjustment, Acceleration/Deceleration Mode Adjustable, Voltmeter Output, Amperometer Output, Multi-Section Speed, Range Sequential operation, pendulum frequency operation, PI closed-loop operation, proportional linkage, remote control
|
Protection function
|
Overvoltage, undervoltage, overcurrent, current limit, overheat, electronic thermal overload relay, overvoltage stall, data protection
|
output signal
|
The fault relay signal can be programmed open collector output, 14 functions can be selected analog output signal: DC 0~10V or 4~20mA, 4 functions can be selected.
|
Display
|
keyboard
|
Parameter setting
|
Functional code, data, status
|
Operation display
|
trouble display
|
Conditions of use
|
Installation site
|
Indoor, no more than 1000 meters above sea level, no dust, no corrosive gas, no direct sunlight
|
Applicable environment
|
- 10 +40 (bare machine is -10 +50), 20%~90% RH (no condensation)
|
Vibration
|
Less than 0.5g
|
Storage mode
|
-25℃~+65℃
|
Installation mode
|
Wall-mounted, floor-mounted electronic control cabinet
|
Protection level
|
IP20
|
Cooling mode
|
0.75KW and below are closed self-cooling, others are forced air-cooling.
|